CC Series High-Output UV systems are designed
specifically for UV disinfection of cooling coils in HVAC applications. The UV
systems can be mounted in various configurations to irradiate cooling coils and drain pans
and for optimum air decontamination. Individual UV fixtures can be mounted to
plenum walls or multiple fixtures can mount to frame assemblies that span supply
ducts or cooling coils. This type of UV systems has been incorporated in the
UV Facilities Standards for the Public Buildings
by the U.S. General Services Administration Office of the Chief Architect.
Applications: Coil Clean (CC) Series UV fixtures are ideal for internal
installation in medium to large HVAC systems in commercial, industrial, health
care and institutional buildings. They are an excellent choice for mounting
close to the coil and drain pan areas to continuously disinfect them with
germicidal UV and inhibit the growth of mold and mildew
in these areas.
Water-tight lamp connection
The CC UV Systems are moisture proof and are offered in single and double lamp
configurations. They can be mounted individually or in built-up banks, or in
parallel rack-system configurations in a variety of locations, including coils,
drain pans, ductwork, mixed air plenums and exhaust systems. The CC fixtures are
available in 18”, 24”, 36”, 48” and 60” lengths and 115, 208, 230 or 277VAC
voltage options, providing installation flexibility to accommodate virtually any
HVAC system.
The CC fixtures are designed for moisture-proof applications with UVC lamps that
incorporate a built-in outer quartz sleeve with protective boot on the power end
for sealing purposes.
Connect the fixtures to 1 power source
Power is brought to the lamp with coated lead wires
through a waterproof connector that is securely sealed to the lamp. The UV lamps
are rated for two-year continuous operational life with approximately 20% drop
in UVC output at end of lamp life.
Features and Benefits of CC germicidal UV systems installation:
SPECIFICATIONS: Every CC UV System is manufactured and factory assembled in the
USA and tested prior to shipment. Each UV fixture consists of housing,
reflector, electronic ballast(s), lamp bracket, plug-in power
connectors and high output UV lamp(s).
FIXTURE: The housings of the UV systems are constructed of heavy gauge hospital grade
stainless steel. Reflectors are fabricated from the highest grade
bright annealed polished stainless steel, which has a reflectivity
rate of 88% when exposed to short-wave UVC in the range of 254 nm.
All components are in one integrated assembly to maximize serviceability.
Custom UV rack
CUSTOM UV RACKS: Custom UV configurations available to meet any requirements.
Multiple-lamp racks, as shown on the picture, can be custom designed and built
for any coil or air handler.
BALLAST: The solid-state electronic
ballast (furnished with this series), is a Class P rapid start with a power
factor minimum of .95. It is available for 120, 208, 230, or 277VAC 50/60Hz and
is designed to maximize photon production in air temperatures of 35º to 175º F.
Minimum ballast start temperature is minus 20º F. Ballasts have an RFI - EMI rating as defined by FCC part 18A for industrial /
commercial applications in regards to suppression. Ballasts are UL listed and
suitable for use in air handling spaces.
LAMPS: CC Series UVC lamps are high-output (800mA), T5 tube diameter, and
constructed from hard glass tubing for superior UV transmittance. Lamps are
“green”, containing ≤8mg of mercury (Hg) and they produce no ozone. Lamps shall
retain, at minimum, 80% of initial output after 17,000 hours of use. They are
sealed for moisture protection with a water-tight connection. Electrodes are
designed to maximize plasma convection and stability for superior lamp
performance. Lamps are rated to produce 11.7µW/cm² per linear inch of lamp arc
length at 1m in airstreams of 400FPM velocities at temperatures of 45º F.
INDEPENDENT TESTING: Units are tested in accordance with the general provisions
of IES Lighting Handbook, 1981 Applications Volume, and provide output per 1"
arc length of not less than 11.7µW/cm² at 1m in a 400FPM airstream of 45° F.
CC UV Air Cleaners and Surface Sterilizers Technical Data
|