UV PRODUCTS
|
 |
|
Duct Cleaners - DC UV Air
Purifiers Specifications |
Tested
and proven performers DC In-Duct UV
Air Purifiers
consist of four or two high output
ultraviolet lamps, ballast and accessory assembly, providing
architects and engineers with a complete duct cleaner to meet all
requirements. The DC UV systems are manufactured in different series
for commercial and industrial installations. All DC UV air cleaners
include voltage specific units for 120/277V, 60Hz or 220V, 50Hz.
Individually or in combination with like units and/or Coil Clean
(CC) UV disinfection systems, the DC in-duct UV air cleaners adapt to HVAC and exhaust
systems.The DC UV air purifiers can be installed during or after construction by cutting a small hole in the duct wall for
UV lamp insertion and fastening the transformer section to the exterior wall surface. The
UV air purifiers mounting surface features an airtight gasket. A simple support bracket
for the UV lamps is available for large plenum chambers.
DC In-Duct UV Air Purifiers play an important part in preventing the spread of indoor airborne infections. Tests reveal that the disinfected indoor air can have a
microbial count lower than that of outdoor air. UV Duct Cleaners have proved necessary in food plants, pharmaceutical production, hospitals and laboratories.
In-Duct UV Applications:
DC45 Series - Large Duct Heavy
Commercial, Industrial Installations
DC33 Series - Large Duct Commercial, Industrial Installations
DC24 Series - Medium Duct Commercial, Light Industrial Installations
DC16 Series - Medium Duct Light Commercial Installations
DC14 Series – Small/Medium Duct Light Commercial Installations
UV Sizing Instructions for DC Systems
Print
the DC UV Air Cleaners Technical Specs
Print
the DC UV Systems Installation Instructions |
|
UV Air Purifiers Technical Data
The High Output In-Duct DC UV air cleaners are
designed to attach to air ducts and the UV lamps inserted in the air ducts. DC
air cleaners are constructed of high grade stainless steel, utilizing two or four high
output germicidal UV lamps. The DC UV fixtures are available in 120/230/277V,
50/60Hz. Please, specify voltage when ordering. All DC air cleaners use SBL
high output germicidal UV lamps
effective for 17,000 hours.
Duct Cleaners - DC
In-Duct UV Models |
Duct Cleaners - DC -
Description |
UVC Intensity * µW/cm² @1m |
Click on the model for dimensional
drawings |
DC-14 For 14" Air Duct Insertion |
|
DC14-2-120/230/277 |
DC UV air cleaner with two 14" high
output UV lamps SBL410 |
198 |
DC14-4-120/230/277 |
DC UV air cleaner with four 14" high
output UV lamps SBL410 |
396 |
SBL410 |
14" high output replacement UV lamp.
Lamp life 17,000 hours. |
99 |
|
DC-16 For 16" Air Duct Insertion |
|
DC16-2-120/230/277 |
DC UV air cleaner with two 16" high
output UV lamps SBL430 |
234 |
DC16-4-120/230/277 |
DC UV air cleaner with four 16" high
output UV lamps SBL430 |
468 |
SBL430 |
16" high output replacement UV lamp.
Lamp life 17,000 hours. |
117 |
|
DC-24 For 24" Air Duct Insertion |
|
DC24-2-120/230/277 |
DC UV air cleaner with two 24" high
output UV lamps SBL415 |
378 |
DC24-4-120/230/277 |
DC UV air cleaner with four 24" high
output UV lamps SBL415 |
756 |
SBL415 |
24" high output replacement UV lamp.
Lamp life 17,000 hours. |
189 |
|
DC-33 For 33" Air Duct Insertion |
|
DC33-2-120/230/277 |
DC UV air cleaner with two 33" high
output UV lamps SBL420 |
544 |
DC33-4-120/230/277 |
DC UV air cleaner with four 33" high
output UV lamps SBL420 |
1,088 |
SBL420 |
33" high output replacement UV lamp.
Lamp life 17,000 hours. |
272 |
|
DC-45 For 45" Air Duct Insertion |
|
DC45-2-120/230/277 |
DC UV air cleaner with two 45" high
output UV lamps SBL445 |
760 |
DC45-4-120/230/277 |
DC UV air cleaner with four 45" high
output UV lamps SBL445 |
1,520 |
SBL445 |
45" high output replacement UV lamp.
Lamp life 17,000 hours. |
380 |
|
UV Lamp Operation Indicators |
|
TBG070 |
Tube Guard indicator - UV lamp
electrically operating - per ballast 120V 60Hz |
|
TBG070 220 |
Tube Guard indicator - UV lamp
electrically operating - per ballast 220V 50Hz |
|
|
High Output Electronic Ballasts |
|
TXG270 |
120V Ballast for 2 SBL405,430,415 or
1 SBL420,445 lamps |
|
TXG275 |
230V Ballast for 2 SBL405,430,415 or
1 SBL420,445 lamps |
|
TXG280 |
277V Ballast for 2 SBL405,430,415 or
1 SBL420,445 lamps |
|
|
* Specified UV intensity measured at 45° F at 400FPM
air flow. |
|
|
Print
the DC UV Air Cleaners Technical Specs
Print
the DC UV Systems Installation Instructions |
|
|
UV Sizing Instructions for DC Systems |
|
|

Contact American Air & Water for In-Duct UV Air Cleaners
Custom Grid UV Systems
Custom-Designed Grid Ultraviolet Air Purifiers can be fabricated to suit any
special requirement. Our engineers will be glad to cooperate in
their development. You can request design and fabrication of any ultraviolet air cleaner
or rack UV system to
your specifications.
Unlimited modular combinations are available in semi-custom designs.
Optional Ultraviolet Lamp Monitoring: The tube guards electrically monitor each
germicidal UV lamp's
output. A remote panel alerts personnel to early lamp failure. Each UV lamp requires
one tube guard.
DC Fixtures top ^
|